RETROFIT KIT S.P. TO INTM PILO
T.  1/2"X3/4"

Product #: HON-Y8610U6006

Description

Y8610U kits are for use with natural or LP gas: provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated. •Ignition trail/delay sequence is repeated until the appliance lights or call for heat is removed. Specifications • Description: Provide electronic control of intermittent pilot ignition systems used on gas fired furnaces, boilers, and other heating appliances. •System Type: Intermittent Pilot •Ignition Sequence: Continuous retry, after trial for ignition, pilot gas shuts off for 5 minutes, then another trial for pilot ignition takes place •Typical Gas Control: VR8204, VR8304 •Type of Gas: Natural or LP •Flame Sense: Single Rod or Two Rods •Ignition Source: Internal high voltage spark generator •Prepurge: 0 or 30 seconds •Ignition trials to lockout: continuous retry •Lockout Timing: 15 or 90 seconds •Includes: VR8304M3558 (1/2 x 3/4; 3.5" setting; 270kBtu/hr at 1 in. p.d.)